Product Details
img

YB-12/0.4 Environmental Prefabricated Compact Box-Type/Kiosk Substation

Min.Order : 1 Pieces Quick Quotation >

Conpany Profile

6 YRS Shaanxi XD HI-TECH Medium-Low Voltage Apparatus Co.,Ltd

Transaction Level:
du.juan@xdhi-t.com
+8613689259690

Product Details

Find high quality yb-12/0.4 environmental prefabricated compact box-type/kiosk substation with competitive price here. Please rest assured to buy yb-12/0.4 environmental prefabricated compact box-type/kiosk substation with Shaanxi XD HI-TECH Medium-Low Voltage Apparatus Co.,Ltd

1. General

YB-12/0.4 Environmental Protection Series prefabricated compact Box-type Substation is applicable to high-rise buildings, street frontage substations, urban street lights, villages, oil field, mines, factories, wharfs, parks, shopping malls and temporary device and places. The compact transformer substation has lots of advantages, such as small occupation space, strong set character, short construction duration, less investment, convenient installation and maintenance, lighter weight, shorter power supply radius and movable feature. 

2. Technical Parameters

Items

HV load switch

transformer

LV load switch


Rated capacity(kvA)

50-1000KVA

Rated voltage(kV)

10

10/0.4

0.4

10

Rated current(A)

400

630


630

100

2000

2500

6.3-4

50-100

Breaking current   (effective value)A






50

Rn3

SKL.J

Rn3

SKL.J

22

31.5

20

50

4s thermal stability   current kA(peak)

12.5/2s

20/2s




Dynamic stability current   kA(peak)

31.5

50




Short circuit closed current   kA(peak)

31.5

50




Power frequency withstand   voltage kv/min

To ground 42

Oil immersed TR. 35



Fracture 48

Dry type TR. 28

Lighting impulse withstand   voltage kV

To ground 75




Fracture 85


Upgrade level dB


Oil immerse =55



Dry type =65

Protection grade

IP3X

IP2X

IP3X


3. Operation conditions

  1. Ambient temperature: highest temperature is 40?, the lowest temperature is -25?, highest daily average temperature should be less than 35?.

  2. Relative humidity: daily everage=95%, monthly average =90%.

  3. Outdoor wind speed should be less than 35m/s.

  4. Altitude should be less than 1000m.

  5. The ground inclination is less than 3°.

  6. The installation place should be free from explosion,  fire, chemical corrosion and serious shaking.

   7.  If the equipment will be used in special conditions, coordinate with a manufacturer

4. Test report

YB test report


Recommend Product